|

As with any industrial process, safety is a major concern, especially
with burner/boiler applications. The centerpiece of any burner/boiler
safety system is the Flame Scanner. The following paragraph describes
in detail the light-off sequence of a burner and explains the role of
the Flame Scanner.
- The Burner Management System (BMS), which includes the Scanner and
Signal Processor, is powered up. Once a fuel is selected and the Burner
Start button is pressed, the BMS starts the fan and opens the fan damper
to begin the air purge process. Once the purge cycle has completed,
the BMS drives the air damper to the light-off position. This is typically
20-25% of the burner maximum heat input.
- The BMS then energizes a transformer connected to the pilot electrode,
thereby causing it to begin sparking. At the same time, the BMS checks
the pilot gas supply pressure to ensure that the appropriate heat input
will be delivered to the pilot. Then, the BMS opens the two pilot gas
shutoff valves and closes the pilot gas vent valve (This system is also
know as Double Block and Bleed).
- At this point, the pilot should be lit and the scanner should be receiving
a flame signal from the pilot flame. If the scanner does not pick up
this signal within a 10 second trial for ignition, the BMS will shut
the pilot gas shutoff valves, de-energize the transformer, and end the
start-up sequence.
- If the pilot flame is "seen" by the scanner, the BMS proceeds to check
the following interlocks: Loss of ID Fan, Loss of FD Fan, Combustion
Airflow Low, Excess Furnace Pressure, Loss of Pilot Flame, High Burner
Gas Pressure, Low Burner Gas Pressure. If all interlocks are proven,
the BMS then opens the main gas shutoff valves and closes the main gas
vent valve.
- After a five second trial for ignition, the pilot electrode is de-energized,
the pilot gas shutoff valves are closed, and the pilot gas vent valve
is opened. If the scanner continues to receive a strong flame signal
from the main burner, the system will then be released for modulation.
If the scanner fails to pick up a flame signal from the main burner,
the main gas shut-off valves are closed and the vent valve opened. In
this case, the entire light-off sequence must be re-started.
Back to top
|