California Rule 4306 |
||||||
|
Category |
Operated on
Gas |
Operated on
Liquid Fuel |
||||
|
NOx Limit
|
||||||
| Standard Option |
|
CO Limit |
NOx Limit |
CO Limit |
||
|
A. |
Units with a rated heat input ≤ 20.0 MMBtu/hr,
except for below Categories. |
15 ppmv or
0.018 lb/MMBtu |
9
ppmv or 0.011 LB/MMBtu |
400 ppmv |
40 ppmv or
0.052 LB/MMBtu |
400 ppmv |
|
B. |
Units with a rated heat input > 20.0 MMBtu/hr,
except for below Categories. |
9 ppmv or
0.011 LB/MMBtu |
6
ppmv or 0.007 LB/MMBtu |
400 ppmv |
40 ppmv or
0.052 LB/MMBtu |
400 ppmv |
|
C. |
Oil Field Steam Generators. |
15 ppmv or 0.018 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
D. |
Refinery units with a rated heat input > 5 MMBtu/hr
≤ 65 MMBtu/hr. |
30 ppmv or 0.036 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
E. |
Refinery units with a rated heat input > 65 MMBtu/hr
≤ 110 MMBtu/hr. |
25 ppmv or 0.031 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
F. |
Refinery units with a rated heat input > 110 MMBtu/hr. |
5 ppmv or 0.0062 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
G. |
Load-following units. |
15 ppmv or 0.018 LB/MMBtu |
9
ppmv or 0.011 LB/MMBtu |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
H. |
Units limited by a Permit to Operate to an annual
heat input of 9 – 30 billion Btu/yr. |
30 ppmv or 0.036 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
|
I. |
Units in which the rated heat input of each burner
is ≤ 5 MMBtu/hr, but the total rated heat input of all the burners
in a unit is > 5 MMBtu/hr, as specified in the Permit to Operate,
and in which the products of combustion do not come in contact with
the products of combustion of any other burner. |
30 ppmv or 0.036 LB/MMBtu |
No Option |
400 ppmv |
40 ppmv or 0.052 LB/MMBtu |
400 ppmv |
Exemptions:
The above limits do not apply to a unit when burning any non-PUC quality natural gas during periods of gas curtailment provided:
Exempt Equipment: